Author(s): M.A.A.S. Alyan, Y.H.A. Rahim, and S.M.S. Al-Dhalaan
Article publication date: 1994-08-01
Vol. 12 No. 2 (yearly), pp. 231-253.
DOI:
142

Keywords

superconducting generators, electro-hydraulic governors, turbo-alternators

Abstract

One most important aspect of design of superconducting generators concerns their stability following a major system disturbance. As the superconducting field winding of these generators has a relatively very long time constant, only governor control shall be relied upon to improve their stability. This paper presents the details of design of a state feedback controller, based on pole-placement technique, to improve transient performance of superconducting turbo-alternators, fitted with fast acting electro- hydraulic governors. The results, obtained by computer simulation, establish that such a controller, with a time delay to the control signal, enhances the transient stability of the machine, by rapidly damping the post fault rotor oscillation.